IEC-101 Slave ♦ ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 95 of 159
August 6, 2010
C_RC_NA
A Control Regulating Step Command information object occupies one byte and
uses byte addressing.
For example, if you configured the following points:
The following table describes how these points would be used.
Inf. Object Address Module Database Address
1000 Low Byte of word 250 (Byte address 500)
300 Low Byte of word 20 (Byte address 40. Must match
configuration of point 300 in M_ST_NA.)
1001 Low Byte of word 260 (Byte address 520)
301 Low Byte of word 30 (Byte address 60. Must match
configuration of point 301 in M_ST_NA.)
1002 High Byte of word 270 (Byte address 541)
302 High Byte of word 40 (Byte address 81. Must match
configuration of point 302 in M_ST_NA.)