101S Protocol Configuration IEC-101 Slave ♦ ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 24 of 159 ProSoft Technology, Inc.
August 6, 2010
2.1 [IEC-870-5-101 Port 0]
This section provides information required to configure a slave application with
the gateway.
2.1.1 Enabled
YES or NO
Enables or disables the primary port. If the port is not enabled (No), then the
gateway will not use the port. If the port is enabled (Yes), the gateway will
emulate an IEC 60870-101 slave device on the port.
2.1.2 Time DB Offset
-1, or 0 to 3994
This parameter defines the location in the database where the time maintained
for the IEC protocol is copied. This time is updated whenever a time
synchronization command is received from the host and continually as the
program runs. If the parameter is set to -1, the time will not be placed in the
database.