IEC-101 Slave ♦ ProLinx Communication Gateway IEC 60870-5-101 Slave Interoperability Statement
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 135 of 159
August 6, 2010
6.7 Type Identifier and Cause of Transmission Assignments
(Station-specific parameters)
Shaded boxes: option not required
Black boxes: option not permitted in this companion standard
Blank boxes: functions or ASDU not used
Mark Type Identification/Cause of Transmission combinations: "X" if only used in
standard direction, "R" if only used in reverse direction, and "B" if used in both
directions.
Type Identification Cause of transmission
1 2 3 4 5 6 7 8 9 10 11 12 13 20
to
36
37
to
41
44 45 46 47
<1> M_SP_NA_1 X X X X X
<3> M_DP_NA_1 X X X X X
<5> M_ST_NA_1 X X X X X
<7> M_BO_NA_1 X X X X X
<9> M_ME_NA_1 X X X X X
<11> M_ME_NB_1 X X X X X
<13> M_ME_NC_1 X X X X X
<15> M_IT_NA_1 X X X X
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X
<31> M_DP_TB_1 X
<32> M_ST_TB_1 X
<33> M_BO_TB_1 X
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X X
<47> C_RC_NA_1 X X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X X
<51> C_BO_NA_1 X X X X X X X
<58> C_SC_TA_1 X X X X X X X X X