Reference IEC-101 Slave ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 104 of 159 ProSoft Technology, Inc.
August 6, 2010
M_ME_NB
Monitored Measured Normalized Point Associated Parameter Point
500 2500
501 2501
502 2502
503 2503
504 2504
Controlling the Generation of Events
Some applications may require that only some points should generate events.
Other applications may require that all configured points should generate events.
The gateway offers considerable flexibility for event control. You can control how
events will be generated at 3 different levels:
1 Application Level (all configured points)
2 Data Type Level (all configured points of specific ASDU type)
3 Point Level (each individual point)
General Events (All Points)
You can control how frequently the gateway will scan the database for events
using the following configuration parameter:
If this parameter is set to 0, the gateway will not generate events for any points.
A non-zero value will configure how frequently the gateway will scan for events in
the database.