MVI69-PDPMV1 CompactLogix or MicroLogix Platform Ladder Logic
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 29 of 225
July 8, 2011
3 Fill the module properties as follows:
Parameter Value
Name
Enter a module identification string. Example:
MVI69PDPMV1_2
Description Enter a description for the module. Example: PROFIBUS
DPV1 MASTER
Comm Format
Select D
ATA-INT
Slot
Enter the slot number in the rack where the MVI69-
PDPMV1 module will be located.
Input Assembly Instance
101
Input Size
62 / 122 / 242
Output Assembly Instance
100
Output Size
61 / 121 / 241
Configuration Assembly Instance
102
Configuration Size
0
4 Click OK to confirm. The new module is now visible:
5 Expand the T
ASKS folder, and then expand the MAINTASK folder.
6 On the M
AINPROGRAM folder, click the right mouse button to open a shortcut
menu. On the shortcut menu, choose N
EW ROUTINE.
7 In the New Routine dialog box, enter the name and description of your
routine, and then click OK.