MVI69-PDPMV1 CompactLogix or MicroLogix Platform Reference
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 167 of 225
July 8, 2011
6.3.4 MVI69 Input and Output Data Blocks
The following illustration shows how data, mailbox block, and status data is
transferred between the MVI69-PDPMV1 and the CompactLogix processor.
The blocks transferred between the module and the processor can perform
different tasks, according to the Block ID numbers.
MVI69 Input Data Block
This block contains the PROFIBUS cyclic input data received from the slaves.
240 Words Input Data Block Format (Input Image)
Word Offset
Start End Name Description
0 0 Block ID Block number 1 to 4
1 1 Output Index
Index of Output image to receive (1 to 4 for data, 0 or
-1 if no data)
2 201 Input Data PROFIBUS Input Data
202 202 Last Out Mailbox ID
Last out mailbox message ID processed from output
image
203 203 Last In Mailbox ID Last in mailbox message ID sent in input image
204 204 Last Alarm ID Last alarm message ID sent in input image
205 205 Reserved Reserved for future use
206 207 PROFIBUS CRC PROFIBUS CRC32 value
208 209 Module CRC Module CRC32 value
210 241 Reserved Reserved for future use