ILX34-AENWG POINT I/O Platform Procedures
Wireless Point I/O Adapter Setup Guide
Page 42 of 79 ProSoft Technology, Inc.
July 31, 2009
3.2.10 Example 2 - Direct Connection
In this example, a ControlLogix controller communicates with POINT I/O modules
via the ILX34-AENWG adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data.
Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.
Add the Relay Output Module and Configure for Direct Connection
1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select N
EW MODULE.
2 In the S
ELECT MODULE dialog box, choose the 1734-OW2 relay output
module from the list, and click OK.