MVI69E-MBS CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
ProSoft Technology, Inc. Page 41 of 162
January 6, 2014
2.6.2 Adding a new module in RSLogix 5000
You can place multiple modules in the same rack provided it does not exceed
the power distance rating of the CompactLogix rack (see page 10). Adding an
additional module to the rack is similar to installing a new module earlier in
this chapter. However, the name of the module must be unique.
1 In RSLogix 5000, locate the I/O CONFIGURATION folder. Right click
CompactBus Local and choose NEW MODULE.
2 In the Select Module Type dialog box, select the MVI69L-MBS module as you
did on page 29. If using an AOP is not an option, select GENERIC 1769
MODULE and click Create.