Prosoft-technology MVI69E-MBS Instrukcja Użytkownika Strona 148

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 162
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 147
Reference MVI69E-MBS CompactLogix Platform
User Manual Communication Module
Page 148 of 162 ProSoft Technology, Inc.
January 6, 2014
8-n
Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9972: Response from Module to Processor
Offset
Description
0
Read Block ID: 9972
1
Write Block ID: To be used by the processor in its next Write block.
2
Return code 0=OK, -1=error
3 to (n-1)
Spare
7.4.21 Pass Module Time to Processor Block
Block 9973: Pass Module Time to Processor Block
This block uses the time information of the module to set the processor time.
Block 9973: Request from Processor to Module
Offset
Description
0
Write Block ID: 9973
1 to (n-1)
Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9973: Response from Module to Processor
Offset
Description
0
Read Block ID: 9973
1
Write Block ID: To be used by the processor in its next Write block.
2
Year (0-9999)
3
Month (1-12)
4
Day (1-31)
5
Hour (0-23)
6
Minutes (0-59)
7
Seconds (0-59)
8
Milliseconds
9 to (n-1)
Spare