HART ProLinx Gateway Reference
HART Master Driver Manual
Page 86 of 119 ProSoft Technology, Inc.
July 7, 2009
COMMAND 55 - Write Transmitter Variable Damping Value
Description
This command writes the Damping Value of a user selected transmitter variable.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code
Transmitter Variable Damping Value (Byte
0)
1
Transmitter Variable Damping Value (Byte
1)
Transmitter Variable Damping Value (Byte
2)
2
Transmitter Variable Damping Value (Byte
3)
Transmitter Variable Damping Value (Byte
3)
Floating Point Data Returned
Word High Byte Low Byte
0
1
Transmitter Variable Damping Value
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code 0