Reference HART ProLinx Gateway
Driver Manual HART Master
ProSoft Technology, Inc. Page 85 of 119
July 7, 2009
COMMAND 54 - Read Transmitter Variable Information
Description
This command gets information about any selected transmitter variable sensor.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code Transmitter Variable Code
Floating Point Data Returned
Word High Byte Low Byte
0
1
Transmitter Variable Upper Limit
2
3
Transmitter Variable Lower Limit
4
5
Transmitter Variable Damping Value (Sec)
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code Sensor Serial Number 0
1 Sensor Serial Number 1 Sensor Serial Number 2
2 Unit Code for Limits 0