Reference MVI71-DFNT PLC 5
User Manual EtherNet/IP Client/Server Communication Module
Page 70 of 175 ProSoft Technology, Inc.
February 3, 2011
The MVI71-DFNT module communicates directly over the PLC backplane. Data
is paged between the module and the PLC processor across the backplane using
BTR and BTW operations. Data is transferred from the module to the processor
using the BTR blocks, and data is transferred from the processor to the module
using BTW blocks.
Block Transfer Backplane Data Transfer
The following illustration shows the data transfer method used to move data
between the PLC processor, the MVI71-DFNT module, and the Ethernet
Network.
As shown in the diagram, all data transferred between the module and the
processor over the backplane is through the BTR and BTW blocks. Ladder logic
must be written in the PLC processor to interface the block data with the
module's internal database. All data used by the module is stored in its internal
database. The following illustration shows the layout of the database:
Module’s Internal Database Structure
4000 registers for user data
0
Register Data
3999