3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example: PS69DPS
Description
Enter a description for the module. Example: Profibus DP
Slave Communication Module.
Comm Format
Select Data-INT
Slot
Enter the slot number in the rack where the PS69-DPS
module will be installed.
Input Assembly Instance
101
Input Size
190
Output Assembly Instance
100
Output Size
124
Configuration Assembly Instance
102
Configuration Size
32
4 On the Connection tab, check or un-check, as desired the Major fault option.