5204SE-MNET-PDPMV1 ♦ ProLinx Gateway Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 210 of 235 ProSoft Technology, Inc.
December 22, 2009
4.6.8 Set Slave Address Message Structure
Parameter Description
Command Initiator Application
Command Name FB_APPL_SET_SLAVE_ADDRESS
Command Number 0006h
Fragmented No
Extended Header Data Fault information may be returned in the header of the response.
Command and Response Layout: Set Slave Address
Command Response
Message ID
(ID) (ID)
Acyclic Message Status
Word
4002h 0002h
Command 0006h 0006h Set Slave Address
Data size (Size of data bytes in hex) (Size of data bytes in hex) Number of Slave Data
bytes (n)
Frame count 0001h 0001h
Frame number 0001h 0001h
Offset high 0000h 0000h
Offset low 0000h 0000h
Extended word 1 Current Slave
Address
New Slave
Address
Current Slave
Address
New Slave
Address
Extended word 2 Slave Ident Number Slave Ident Number
Extended word 3 No_Add_Chg No_Add_Chg
Extended word 4 - -
Extended word 5 - Error Code 1 Error Code 2
Extended word 6 - Error Code 3 Error Code 4
Extended word 7 - Return Code
Extended word 8 Fault Information
Message Data Byte 1 Slave Data 1 Slave Data 1
Message Data Byte 2 Slave Data 2 Slave Data 2
Message Data Byte 3 Slave Data 3 Slave Data 3
...
Message Data Byte 'n'
(where 'n' <= 240)
Slave Data 'n' Slave Data 'n'
Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 218).
Current Slave Address
Range 0 to 125
Specifies the current address of the slave.