Reference 5204SE-MNET-PDPMV1 ProLinx Gateway
User Manual Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc. Page 201 of 235
December 22, 2009
Error Code [1 … 4]
If "Return Code" equals 8030h ("Negative indication from lower layer"), status
values according to the DP-specification may be available in "Error Code 1",
Error Codes 2 through 3 are reserved. Refer to Mailbox Messaging Error Codes.
Return Code
Refer to Mailbox Messaging Error Codes.
Fault Information
If "Invalid other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here. Refer to Acyclic
Message Status Word (page 218).
0001h: Address out of range.
000Ah: Failed to execute request. Refer to Return Codes (page 219) for
additional information.
000Bh: Remote station failure. Refer to Return Codes (page 219) for additional
information.
00FFh: gateway not initialized.
Identifier Bytes [1 … n]
Refer to EN50170 Vol. 2 for information on the structure of these bytes. In
addition, refer to the documentation provided with the slave device for more
information.