Page 14 QTS-CLX-PVX September 2009
Configuring the I/O
ClxPvxCfg Software
The QTS-CLX-PVX module is supplied with a Windows configuration tool,
ClxPvxCfg.exe.
Use this configuration tool to:
Switch between monitor and master mode
Autoconfigure the monitor from an attached Control I/O bus
Convert the configuration for master mode
Map I/O data to ControlLogix scheduled connections
Save and load configuration files
Download and upload configurations
Set the RSLinx path to the QTX-CLX-PVX module
Export aliases for I/O data for import into RSLogix 5000, for both master and
monitor modes
Update the module firmware
ClxPvxCfg is an offline configuration tool; any changes must be downloaded to the QTS-
CLX-PVX module.
Setting the Module Name
To set the module name, right click on the QTS-CLX-PVX at the root of the tree and
select Edit Module Properties.