124 Publication LOGIX-AP010B-EN-P - May 2010
Chapter 8 Logix Replacements for S5 Components
Analog Input Modules
The following table suggests Logix replacements for S5 analog input modules
based on number of channels and input ranges.
Siemens S5 Analog Input Modules Logix Analog Input Modules
Cat. No. Channels Range Cat. No. Channels Range
460-4UA13 8 – single See range cards 1756-IF8 8 ± 10.25V
0…10.25V
0…5.125V
0…20.5 mA
465-4UA12 16 – voltage/current See range cards 1756-IF16 16 ±± 10.25V
0…10.25V
0…5.125V
0…20.5 mA
8 – Pt100 resistance See range cards 1756-IR6I 6 1…487 Ω
2…1000 Ω
4…2000 Ω
8…4080 Ω
465-4UA13 16 – voltage/current See range cards 1756-IF16 16 ± 10.25V
0…10.25V
0…5.125V
0…20.5 mA
8 – Pt100 resistance See range cards 1756-IR6I 6 1…487 Ω
2…1000 Ω
4…2000 Ω
8…4080 Ω
463-4UA12 4 – single 0…1V, 10V, 20mA 1756-IF8 8 ± 10.25V
0…10.25V
0…5.125V
0…20.5 mA
463-4UB12 4 - single 4…20mA 1756-IF8 8 ± 10.25V
0…10.25V
0…5.125V
0…20.5 mA