ProLinx-HART ♦ ProLinx Gateway Reference
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 77 of 104
October 13, 2011
COMMAND 55 - Write Transmitter Variable Damping Value
Description
This command writes the Damping Value of a user selected transmitter variable.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code Transmitter Variable Damping Value (Byte
0)
1 Transmitter Variable Damping Value (Byte
1)
Transmitter Variable Damping Value (Byte
2)
2 Transmitter Variable Damping Value (Byte
3)
Transmitter Variable Damping Value (Byte
3)
Floating Point Data Returned
Word High Byte Low Byte
0 Transmitter Variable Damping Value
1
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code 0
Przeglądanie stron 76