Prosoft-technology MVI69-DNP Instrukcja Użytkownika Strona 114

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 113
MVI69-DNP CompactLogix or MicroLogix Platform Reference
DNP 3.0 Master/Slave Communication Module
Page 114 of 129 ProSoft Technology, Inc.
November 3, 2008
OBJECT REQUEST RESPONSE
Obj Var Description Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
2 16-Bit Counter
Change Event
Without Time
129, 130 17, 28 24 Master will process this
variation
3 32-Bit Delta Counter
Change Event
Without Time
40
4 16-Bit Delta Counter
Change Event
Without Time
24
5 32-Bit Counter
Change Event With
Time
88
6 16-Bit Counter
Change Event With
Time
72
7 32-Bit Delta Counter
Change Event With
Time
88
8 16-Bit Delta Counter
Change Event With
Time
72
23 0 Frozen Counter
Event: All Variations
1 32-Bit Frozen
Counter Event
Without Time
40
2 16-Bit Frozen
Counter Event
Without Time
24
3 32-Bit Frozen Delta
Counter Event
Without Time
40
4 16-Bit Frozen Delta
Counter Event
Without Time
24
5 32-Bit Frozen
Counter Event With
Time
88
6 16-Bit Frozen
Counter Event With
Time
72
7 32-Bit Frozen Delta
Counter Event With
Time
88
8 16-Bit Frozen Delta
Counter Event With
Time
72
30 0 Analog Input: All
Variations
1 06 16 Master will generate this
variation
Przeglądanie stron 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 128 129

Komentarze do niniejszej Instrukcji