
Start Here MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 36 of 255 ProSoft Technology, Inc.
March 22, 2011
4 In the Module Properties dialog box, enter the N
AME
,
D
ESCRIPTION
and S
LOT
options for your application, using the examples in the following illustration.
You must select the C
OMM
F
ORMAT
as D
ATA
-
INT in the dialog box. Failure to
set the correct parameters will result in backplane communication problems
between the module and the processor.
5 Click the
C
ONNECTION
tab and change the Requested Packet Interval to
5.0
MS
as shown in the following illustration.
6 Click F
INISH
to save the module into your existing application.
7 Next, open the sample program in RSLogix 5000. Refer to Open the Sample
Program in RSLogix (page 16) to determine the correct version of the sample
program to use.
Komentarze do niniejszej Instrukcji