Contents ILX69-PBM CompactLogix or MicroLogix Platform
User Manual PROFIBUS Master Communication Module
Page 32 of 124 ProSoft Technology, Inc.
February 4, 2015
5.1.2 Module Properties 1
1 The communications parameters for the module are configured in the Module Properties
dialog.
2 Enter PBM as the NAME and enter a short description for the module.
3 Select the Slot number in which the module is installed in the CompactLogix system. It
must be within 2 slots of a power supply.
4 Select Data - INT as the Comm_Format.
5 Set the connection parameters as they are shown in the dialog. The Connection
Parameter SIZE(s) may vary.
Connection Parameter
Assembly Instance
Size (in Words)
Input
101
44 + X (Where X = 0 to 204) = 248 max
Output
100
8 + Y (Where Y = 0 to 240) = 248 max
Configuration
102
0
Note: The Size parameters vary for each PROFIBUS network. You can
customize these values using section Adjusting Input/Output Data Lengths in
the Project 51.
X = Number of Words configured for the ILX69-PBM (PROFIBUS input data); input size can
be in the range between 44 and 248 words
Y = Number of Words configured for the ILX69-PBM (PROFIBUS output data); output size
can be in the range between 8 and 248 words