AN-X-DCSNet2 Page
23
2. Map DCS data to the scheduled data and save the mappings as a
comma separated variable (CSV) file
3. Send the configuration file to AN-X
Requirements
RSLogix 5000 version 12 or above
ControlLogix processor with firmware version 12 or above
100 Mbit Ethernet network and ENBT modules. We strongly
recommend using Ethernet switches rather than hubs
Reference
Allen-Bradley publication EtherNet/IP Media Planning and Installation
Manual, publication ENET-IN001A-EN-P
Configuring AN-X in RSLogix 5000
The AN-X-DCSnet2 emulates a 17-slot 1756 chassis with an ENBT/A in
slot 16 and generic modules in slots 0 to 15.
Exclusive Owner Connection
To configure the AN-X-DCSnet2 in RSLogix 5000:
1. Right click on the ControlLogix Ethernet bridge module that will be
communicating with the AN-X and select Add Module. Add a
1756-ENBT/A module. Set the Major Rev to 1.