May 14, 2014
CONNECTION TIMEOUT: 0 to 1200 seconds. This is the number of seconds the
Server will wait to receive new data. If the Modbus TCP/IP Server does not
receive any new data during this time, it will close the Ethernet socket
connection. The default value is 60.
The gateway supports multiple MNET servers and MBAP servers.
ENCAPSULATED MODBUS: This is the number of Modbus TCP/IP Client devices
that will communicate with the gateway using TCP/IP Service Port 2000. These
are devices that use Modbus RTU serial-style message structures enclosed in an
Ethernet wrapper.
MBAP : This is the number of Modbus TCP/IP Client devices that will
communicate with the gateway using Schneider Electric MBAP-style messages
on TCP/IP Service Port 502.
2.2.1 Modbus TCP/IP Client and Server - Lookup