June 23, 2009
5.1.2 Hardware Specifications
Specification Description
Form Factor
Single Slot 1771 chassis compatible
BTR/BTW data transfer
Local or remote rack
Backplane current load 800 mA @ 5 V
Operating temperature 0 to 60°C (32 to 140°F)
Storage temperature -40 to 85°C (-40 to 185°F)
Shock 30g operational
50g non-operational
Vibration 5 g from 10150 Hz
Relative humidity 5% to 95% (non-condensing)
LED Indicators Module status
Backplane transfer status
Application status
Serial activity and error LED status
Configuration Serial port (CFG) DB-9M PC compatible
RS-232
Hardware handshaking
Ethernet Port (Ethernet modules) RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s,
applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to
5000 [ARP] frames-per-second and less than or equal to 5
minutes duration
5.1.3 Functional Specifications
10/100 MB Ethernet Application port
Supports Enron version of Modbus protocol for floating point data
transactions
PCB includes a powerful Modbus network analyzer
Special functions (command control, event commands, status, etc.) are
supported by message transfer (unscheduled) using the MSG instruction
Configurable parameters for the client including a minimum response delay of
0 to 65535 ms and floating point support
Supports five independent server connections for Service Port 502
Supports five independent server connections for Service Port 2000
All data mapping begins at Modbus register 40001.
Error codes, network error counters, and port status data available in user
data memory