MVI46-MCM SLC Platform Configuring the MVI46-MCM Module
Modbus Communication Module User Manual
ProSoft Technology, Inc. Page 21 of 108
March 29, 2011
Port 2 Setup
File M0 Offset Register Content Description
N10:40 41 5040 Enable This parameter defines if this port will be used. If the
parameter is set to 0, the port is disabled. A value of 1
enables the port.
N10:41 42 5041 Type This parameter defines if the port emulates a master or
slave device. Enter 0 to emulate a master device and 1
to emulate a slave device.
N10:42 43 5042 Float Flag This flag specifies if the floating-point data access
functionality is to be used. If the float flag is set to Y,
Modbus functions 3,6, and 16 will interpret floating point
values for registers as specified by the two following
parameters.
N10:43 44 5043 Float Start This parameter defines the first register of floating-point
data. All requests with register values greater than or
equal to this value will be considered floating-point data
requests. This parameter is only used if the Float Flag
is enabled. For example, if a value of 7000 is entered,
all requests for registers 7000 and above will be
considered floating-point data.
N10:44 45 5044 Float Offset This parameter defines the start register for floating-
point data in the internal database. This parameter is
only used if the Float Flag is enabled. For example, if
the Float Offset value is set to 3000 and the float start
parameter is set to 7000, data requests for register
7000 will use the internal Modbus register 3000.
N10:45 46 5045 Protocol 0=RTU, 1=ASCII
N10:46 47 5046 Baud Rate This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200. Exceptions: 38400 baud, enter 384. 57600
enter 576. 115000 enter 115.
N10:47 48 5047 Parity This is the parity code to be used on the port. The
coded values are as follows:
0=None
1=Odd
2=Even
N10:48 49 5048 Data Bits This parameter sets the number of data bits for each
word used by the protocol. Enter a value in the range of
5 to 8.
N10:49 50 5049 Stop Bits This parameter sets the number of stop bits for each
data value sent. Enter a value of 1 or 2.
N10:50 51 5050 RTS On Delay This parameter sets the number of milliseconds to
delay after RTS is asserted before the data will be
transmitted. Enter a value in the range of 0 to 65535.
N10:51 52 5051 RTS Off Delay This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the RTS
modem signal will be set low. Enter a value in the range
of 0 to 65535.