QTS-CLX-APACS Page 35
The QTS-CLX-APACS Module Properties dialog box appears. It shows the required
connections and the minimum connection sizes.
In the example shown, the required connections are:
connection 0 with type SINT, minimum input size 60 and minimum output size 9
connection 8 with type REAL, minimum input size 37 and minimum output size 1
In addition, connection 9 is always shown, although it is not required. Connection 9 is
used for module diagnostics. It is recommended that you always create connection 9,
with the sizes shown.
Aliases
The configuration tool creates aliases for I/O data that can be exported and imported into
RSLogix 5000.
Write programs using these aliases rather than using absolute addresses. If the mapping
of the I/O data changes, simply reimport the new aliases and the program will point to the
new data locations.
To export aliases, select Files/Export Alias File