Prosoft-technology 5201-MNET-ASCII Instrukcja Użytkownika Strona 28

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 78
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 27
Modbus TCP/IP Protocol Configuration MNET ProLinx Gateway
Driver Manual Modbus TCP/IP Interface Module
Page 28 of 78 ProSoft Technology, Inc.
September 1, 2010
2.5.7 Swap Code
NONE
S
WAP WORDS
S
WAP WORDS & BYTES
S
WAP BYTES
This parameter defines if and how the order of bytes in data received or sent is to
be rearranged. This option exists to allow for the fact that different manufacturers
store and transmit multi-byte data in different combinations that do other
manufacturers. This parameter is helpful when dealing with floating-point or other
multi-byte values, as there is no one standard method of storing these data
types. This parameter can be set to rearrange the byte order of data received or
sent into order more useful or convenient for other applications. The following
table defines the valid Swap Code values and the effect they have on the byte-
order of the data.
Swap Code Description
None No Change is made in the byte ordering (1234 = 1234)
Swap Words The words are swapped (1234=3412)
Swap Words & Bytes The words are swapped then the bytes in each word are swapped
(1234=4321)
Swap Bytes The bytes in each word are swapped (1234=2143)
These swap operations affect 4-byte (or 2-word) groups of data. Therefore, data
swapping using these Swap Codes should be done only when using an even
number of words, such as when 32-bit integer or floating-point data is involved.
2.5.8 Node IP Address
xxx.xxx.xxx.xxx
The IP address of the device being addressed by the command.
2.5.9 Service Port
502 or other supported ports on server
Use a value of 502 when addressing Modbus TCP/IP servers that are compatible
with the Schneider Electric MBAP specifications (this will be most devices). If a
server implementation supports another service port, enter the value here.