IEC-60870-5-104 (104S) Protocol Implementation 104S v2 ProLinx Gateway
Protocol Manual (Firmware v2.xx)
ProSoft Technology, Inc. Page 61 of 157
M_ME_NC and M_IT_NA
The monitored measured short floating point and monitored integrated total
points occupy two words with double-word addressing.
For example, if you configured the following points:
The following table describes how these points would be stored in the gateway
memory database.
Inf. Object Address Gateway Database Address
500 Words 40 and 41 (Double-word address 20)
501 Words 64 and 65 (Double-word address 32)
502 Word 104 and 105 (Double-word address 52)